| 3 | Utility Lock | The Utility Lock Con!guration Set command enables or disables the utility lock. If the utility lock is enabled, the setpoint cannot be modi!ed directly via the thermostat screen. | 0 | 1 | 0 | 0 | 0 | | From | To | Description |
|---|
| 0 | 255 | 0 = Disabled, 1 - 255 = Enabled |
|
| 8 | Thermostat Differential Temperature | The Thermostat Differential Temperature configuration command sets the differential temperature for multi-stage HVAC systems. | 0 | 2 | 0 | 0 | 4 | | From | To | Description |
|---|
| 2 | 6 | The thermostat differential temperature is in units of 0.5 degrees Fahrenheit. | | 0 | 1 | 0x00 (Heat) or Cool (0x01) |
|
| 9 | Thermostat Recovery Mode | The Thermostat Recovery Mode configuration command sets the HVAC recovery mode type. The recovery mode determines when additional HVAC stages are turned of as the ambient temperature returns to the target temperature. | 0 | 1 | 0 | 0 | 2 | | From | To | Description |
|---|
| 1 | 2 | 1 = Fast, 2 = Economy |
|
| 10 | Temperature Reporting Filter | The Temperature Reporting Filter configuration command sets upper and lower bounds of the ambient temperature reporting. | 0 | 1 | 0 | 0 | 0 | | From | To | Description |
|---|
| 0 | 31868 | Byte 1: 0 -124 (lower bound), Byte 2: 0-124 (upper bound) |
|
| 1 | Temperature Reporting Threshold | The Temperature Reporting Threshold Con!guration Set Command sets the reporting threshold for Reporting Threshold changes in the ambient temperature as detected by the thermostat. | 0 | 1 | 0 | 0 | 2 | |
| 2 | HVAC Settings | The HVAC Settings Configuration Report Command returns the current HVAC con!guration. The HVAC settings must be !xed before the thermostat is joined to the Z-Wave network. | 0 | 4 | 0 | 0 | 0 | | From | To | Description |
|---|
| 0 | 2147483647 | Byte 1: normal (1) or heat pump (2). Byte 2, Bits 7-4: Gas (1) or Electric (2). Byte 2, Bits 3-0: # of Auxiliary Stages. Byte 3: # of Heat Pump Stages. Byte 4: # of Cool Stages. |
|
| 4 | C-Wire/Battery | The C-Wire / Battery Status Con!guration Report Command returns the status of the thermostat power source. The power state is fixed when the thermostat joins the network. | 0 | 1 | 0 | 0 | 0 | | From | To | Description |
|---|
| 1 | 2 | 1=C-Wire, 2=Battery |
|
| 5 | Humidity Reporting Threshold | The Humidity Threshold Con!guration Set Command sets the reporting threshold for changes in the relative humidity as detected by the thermostat. | 0 | 1 | 0 | 0 | 5 | | From | To | Description |
|---|
| 0 | 3 | 0 = Disabled, 1 = 3% RH, 2 = 5% RH, 3 = 10% RH |
|
| 6 | Auxiliary/Emergency Mode | The Auxiliary/Emergency con!guration command enables or disables auxiliary / emergency heating in the thermostat. | 0 | 1 | 0 | 0 | 0 | | From | To | Description |
|---|
| 0 | 1 | 0 = Disabled, 1 = Enabled |
|
| 7 | Thermostat Swing Temperature | The Thermostat Swing Temperature configuration command sets swing temperature on the Temperature thermostat. | 0 | 1 | 0 | 0 | 2 | | From | To | Description |
|---|
| 1 | 8 | 1 = 0.5, 2 = 1.0, 3 = 1.5, 4 = 2.0, 5 = 2.5, 6 = 3.0, 7 = 3.5, 8 = 4.0 |
|