Z-Wave Products

There are over 4107 interoperable Z-Wave products throughout the world, and over 94 million Z-Wave products have been sold since our beginnings in 2001. All of them work together regardless of brand, because they're all based on the common Z - Wavestandard.Browse our Product Finder to see what Z -Wave can do for you.

Z-Wave Configuration Capabilities

Model: Remote Temperature and Humidty (RTH100Z)

Z-Wave Certification Number: ZC10-17115888


Parameter Number

Parameter Size

Parameter Name

Parameter Values

1 1 Time between sending Battery Reports in Hours 1 to 127 1 – 127 hours
  0
(Default)
Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

10 1 Group2 Temperature Delta Autosend Threshold 1 to 50
(Default)
In tenths of degrees
  0 Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

11 1 Group2 Periodic Temperature Send Interval 1 to 120 Minutes
  0
(Default)
Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

12 1 Send Basic Set On above humidity 0 to 100
(Default)
Percent
  0
(Default)
Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

13 1 Send Basic Set On below humidity 0 to 100
(Default)
Percent
  0
(Default)
Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

14 1 Send Basic Set Off above humidity 0 to 100
(Default)
Percent
  0
(Default)
Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

15 1 Send Basic Set Off below humidity 0 to 100
(Default)
Percent
  0
(Default)
Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

16 1 Group1- Humidity Delta Autosend Threshold 1 to 50
(Default)
Percent

Parameter Number

Parameter Size

Parameter Name

Parameter Values

17 1 Group1- Periodic Humidity Send Interval 1 to 120 Minutes
  0
(Default)
Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

18 1 Group3- Humidity Delta Autosend Threshold 1 to 30
(Default)
Percent
  0 Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

19 1 Group3- Periodic Humidity Send Interval 1 to 120 Minutes
  0
(Default)
Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

2 1 Send Basic Set On above temp 15 to 120 15 – 120 Degrees F
  121
(Default)
Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

20 1 Basic Set Options for Temp and Humidity 2 Enable Configuration Registers 2, 5, 13, 14
  1
(Default)
Enable Configuration Registers 2, 5, 12, 15
  3 Enable Configuration Registers 3, 4, 12, 15
  4 Enable Configuration Registers 3, 4, 13, 14

Parameter Number

Parameter Size

Parameter Name

Parameter Values

21 1 Temp offset 249 to 7 Degrees(-7 to 7)

Parameter Number

Parameter Size

Parameter Name

Parameter Values

22 1 Humidity offset 249 to 7 Percent(-7 to 7)

Parameter Number

Parameter Size

Parameter Name

Parameter Values

23 1 Humidity Filter Time Constant 1 to 60
(Default)
Minutes

Parameter Number

Parameter Size

Parameter Name

Parameter Values

3 1 Send Basic Set On below temp 15 to 120 15 – 120 Degrees F
  121
(Default)
Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

4 1 Send Basic Set On below temp 15 to 120 15 – 120 Degrees F
  121
(Default)
Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

5 1 Send Basic Set Off below temp 15 to 120 15 – 120 Degrees F
  121
(Default)
Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

6 1 Make multiple attempts for all Basic Set Commands 1 to 5 Number of extra attempts sent every minute after first send
  0
(Default)
Disabled

Parameter Number

Parameter Size

Parameter Name

Parameter Values

7 1 Temp Units 1
(Default)
Fahrenheit
  0 Celsius

Parameter Number

Parameter Size

Parameter Name

Parameter Values

8 1 Group1 Temperature Delta Autosend Threshold 1 to 200
(Default)
In tenths of degrees

Parameter Number

Parameter Size

Parameter Name

Parameter Values

9 1 Group1 Periodic Temperature Send Interval 1 to 120 Temperature Send Interval (minutes)
  0
(Default)
Disabled