Z-Wave Products

There are over 4408 interoperable Z-Wave products throughout the world, and over 94 million Z-Wave products have been sold since our beginnings in 2001. All of them work together regardless of brand, because they're all based on the common Z - Wavestandard.Browse our Product Finder to see what Z -Wave can do for you.

Z-Wave Configuration Capabilities

Model: Smart Meter (ZMNHTD1)

Z-Wave Certification Number: ZC10-18086203


Parameter Number

Parameter Size

Parameter Name

Description

40 1 Reporting Watts on power change • Default value 10 • 0 – reporting disabled • 1-100 = 1% - 100% reporting enabled. Power is reported only when actual power in Watts (in real time changes for more than set percentage comparing to previous actual power in Watts, step is 1%. NOTE: when power is changed for more than percent value in this parameter -> the device is reporting also: • A (Current) (if the value has changed) • V (Voltage) (if the value has changed) • Power Factor (if the value has changed) • kvar (Reactive power) (if the value has changed) • kWh (Energy – Active power accumulated Import) (if the value has changed) • kWh (Energy – Active power accumulated Export) (if the value has changed) • kVAh (Energy – Apparent power accumulated) (if the value has changed) • kvarh (Energy – Reactive power accumulated) (if the value has changed) To avoid unintended reporting (electric disturbances, noise, etc..) the measured power less than 5W is not reported.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

10 0 100 No No No

From

 

To

Description

0   0 reporting disabled
1   100 1% - 100% reporting enabled. Power is reported only when actual power in Watts (in real time changes for more than set percentage comparing to previous actual power in Watts, step is 1%.

Parameter Number

Parameter Size

Parameter Name

Description

42 2 Reporting on time interval • Default value 600 (10 minutes) • 0-599 = reporting disabled • 600 - 32535 = 600 seconds - 32535 seconds. Reporting enabled. Report is send with the time interval set by entered value. NOTE: The device is reporting the following values: • W (Active Power) (if the value has changed) • A (Current) (if the value has changed) • V (Voltage) (if the value has changed) • Power Factor (if the value has changed) • kvar (Reactive power) (if the value has changed) • kWh (Energy – Active power accumulated Import) (if the value has changed) • kWh (Energy – Active power accumulated Export) (if the value has changed) • kVAh (Energy – Apparent power accumulated) (if the value has changed) • kvarh (Energy – Reactive power accumulated) (if the value has changed)

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

600 0 32535 No No No

From

 

To

Description

0   599 reporting disabled
600   32532 Reporting enabled. Report is send with the time interval set by entered value.

Parameter Number

Parameter Size

Parameter Name

Description

45 1 Reset Power counters • Default value 0 • 0 – no function • 1 – reset counter 1 –kWh import • 2 – reset counter 2 – kvarh • 4 – reset counter 3 – kVAh • 8 – reset counter 4 – kWh export • 15 – reset ALL counters

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 15 No No No

From

 

To

Description

0   0 no function
1   1 reset counter 1 –kWh import
2   2 reset counter 2 – kvarh
4   4 reset counter 3 – kVAh
8   8 reset counter 4 – kWh export
15   15 reset ALL counters