Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
1 | 1 | HVAC Type | 0 (Default) |
Normal | |
1 | Heat Pump | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
10 | 4 | Balance Setpoint | 0 to 95 (Default) |
Balance Setpoint | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
12 | 2 | Fan Circulation Period | 1 to 1440 (Default) |
Fan Circulation Period | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
13 | 1 | Fan Circulation Duty Cycle | 0 to 100 (Default) |
Duty Cycle | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
14 | 2 | Fan Purge Time | 1 to 3600 (Default) |
Fan purge time | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
15 | 4 | Maximum Heat Setpoint | 35 to 95 (Default) |
Maximum Heat Setpoint | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
16 | 4 | Minimum Heat Setpoint | 35 to 95 (Default) |
Minimum Cool Setpoint | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
17 | 4 | Maximum Cool Setpoint | 50 to 95 (Default) |
Maximum Cool Setpoint | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
18 | 4 | Minimum Cool Setpoint | 35 to 95 (Default) |
Minimum Cool Setpoint | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
19 | 1 | Thermostat Lock | 0 (Default) |
Disabled | |
1 | Full Lock | ||||
2 | Partial Lock | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
2 | 1 | Number of Heat Stages | 0 to 3 (Default) |
Number of Heat Stages | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
20 | 1 | Compressor Delay | 0 to 60 (Default) |
Minutes | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
23 | 1 | Temperature Display Units | 0 | Celsius | |
1 (Default) |
Fahrenheit | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
24 | 1 | HVAC Modes Enabled | 3 | Off, Heat | |
5 | Off, Cool | ||||
7 | Off, Heat, Cool | ||||
15 (Default) |
Off, Heat, Cool, Auto | ||||
31 | Off, Heat, Cool, Auto, Emergency Heat | ||||
23 | Off, Heat, Cool, Emergency Heat | ||||
19 | Off, Heat, Emergency Heat | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
25 | 2 | Configurable Terminal Settings | 0 (Default) |
None | |
1 | W3 | ||||
2 | Humidifier | ||||
3 | Dehumidifier | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
26 | 1 | Power Source | -128 to 127 (Default) |
No Change - Read-Only Parameter | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
27 | 1 | Low Battery Alert Threshold | 0 to 100 (Default) |
Low Battery Alert Threshold | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
28 | 1 | Very Low Battery Alert Threshold | 0 to 100 (Default) |
Very Low Battery Alert Threshold | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
29 | 4 | Relay State | 0 to 65535 (Default) |
Relay State | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
3 | 1 | Number of Cool Stages | 0 to 2 (Default) |
Number of Cool Stages | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
30 | 2 | Remote temperature enable | 0 (Default) |
Disabled | |
1 | Enabled | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
31 | 4 | Heat Differential | 10 to 100 (Default) |
Heat Differential | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
32 | 4 | Cool Differential | 10 to 100 (Default) |
Cool Differential | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
33 | 4 | Temperature Reporting Threshold | 5 to 20 (Default) |
Temperature Reporting Threshold | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
35 | 1 | Z-Wave Echo Association Reports | 0 (Default) |
Disabled | |
1 | Enabled | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
36 | 4 | C-Wire Power Thermostat Offset | 0 to 10 (Default) |
Fahrenheit | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
37 | 1 | Run Fan with Auxiliary Heat | 0 (Default) |
Disabled | |
1 | Enabled | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
38 | 4 | Z-Wave Association Report Bitmask | 1 | Thermostat Mode bitmask | |
8 | Thermostat Operating State bitmask | ||||
16 | Thermostat Fan Mode bitmask | ||||
32 | Thermostat Fan State bitmask | ||||
64 | Ambient Temperature bitmask | ||||
128 | Relative Humidity bitmask | ||||
512 | Battery Low Notification bitmask | ||||
1024 | Battery Very Low Notification bitmask | ||||
2048 | Thermostat Supported Modes bitmask | ||||
4096 | Remote Enable Report bitmask | ||||
8192 | Humidity Control Operating State bitmask | ||||
16384 | HVAC Type bitmask | ||||
32768 | Number of Cool/Pump Stages | ||||
65536 | Number of Heat/Aux Stages bitmask | ||||
131072 | Relay Status bitmask | ||||
262144 | Power Source bitmask | ||||
524288 | Notification Report Power Applied bitmask | ||||
1048576 | Notification Report Mains Disconnected bitmask | ||||
2097152 | Notification Report Mains Reconnected bitmask | ||||
4194394 | Notification Report Replace Battery Soon bitmask | ||||
8388608 | Notification Report Replace Battery Now bitmask | ||||
16777216 | Notification Report System Hardware Failure bitmask | ||||
33554432 | Notification Report System Software Failure bitmask | ||||
67108864 | Notification Report System Hardware Failure with code bitmask | ||||
134217728 | Notification Report System Software Failure with Code bitmask | ||||
268435456 | Display Units bitmask | ||||
536870912 | Heat Fuel Type bitmask | ||||
1073741824 | Humidity Control Mode bitmask | ||||
-2147483648 | Humidity Control Setpoint bitmask | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
39 | 2 | Remote Temperature Timeout | 0 to 32767 (Default) |
minutes | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
4 | 1 | Heat Fuel Type | 0 | Fossil | |
1 (Default) |
Electric | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
40 | 4 | Remote Temperature Differential | 0 to 99 (Default) |
Farhenheit | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
41 | 1 | Remote Temperature ACK Failure Limit | 0 to 127 (Default) |
Retries | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
42 | 1 | Remote Temperature Display Enable | 0 | Disabled | |
1 (Default) |
Enabled | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
43 | 2 | Outdoor Temperature Timeout | 0 to 32767 (Default) |
Minutes | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
45 | 2 | Heat Pump Expire | 0 to 2880 (Default) |
Minutes | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
46 | 4 | Dehumidify by AC Offset | 0 to 10 (Default) |
Farhenheit | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
48 | 1 | PIR Enable | 0 | Disabled | |
1 (Default) |
Enabled | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
49 | 1 | Display Options | 0 (Default) |
Do not show Humidity | |
1 | Show Humidity | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
5 | 4 | Calibration Temp | -10 to 10 (Default) |
Calibration Temperature | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
50 | 4 | System Configuration | -2147483648 to 2147483647 (Default) |
No Change - Read-Only Parameter | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
51 | 2 | Thermostat Reset | 2870 (Default) |
Magic Value | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
52 | 1 | Vent Options | 0 | Disabled | |
1 | Always activate regardless of thermostat operating state | ||||
2 | Only activate vent when the thermostat operating state is heating. | ||||
3 | Only activate vent when the thermostat operating state is cooling | ||||
4 (Default) |
Only activate vent when the thermostat operating state is heating or cooling | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
53 | 2 | Vent Circulation Period | 10 to 1440 (Default) |
Minutes | |
0 | Disabled | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
54 | 1 | Vent Circulation Duty Cycle | 0 to 100 (Default) |
Duty Cycle | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
55 | 4 | Vent Maximum Outdoor Temperature | -1 (Default) |
Disabled | |
0 to 99 | Fahrenheit | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
56 | 4 | Vent Minimum Outdoor Temperature | -1 (Default) |
Disabled | |
0 to 99 | Fahrenheit | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
57 | 1 | Relay Harvest Level | 0 | Off | |
9 | 8 Pulses | ||||
10 | 16 Pulses | ||||
11 | 32 Pulses | ||||
12 (Default) |
64 pulses | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
58 | 1 | Relay Harvest Interval | 0 | Off | |
2 | 4 Milliseconds | ||||
3 | 8 Milliseconds | ||||
4 (Default) |
16 Milliseconds | ||||
5 | 32 Milliseconds | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
59 | 1 | Minimum Battery Reporting Interval | 0 to 127 (Default) |
Hours | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
6 | 4 | Swing | 0 to 30 (Default) |
Swing | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
60 | 1 | Humidity Control Swing | 1 to 100 (Default) |
Percent Relative Humidity | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
61 | 1 | Minimum Humidity Reporting Threshold | 0 to 100 (Default) |
Percent Relative Humidity | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
62 | 1 | Z-Wave Send Fail Limit | 1 to 127 (Default) |
Send Failures | |
0 | Disabled | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
63 | 2 | Z-Wave Listen Before Talk Threshold | 0 to 32767 (Default) |
Listen before talk threshold | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
64 | 1 | Vent Override Lockout | 0 to 127 (Default) |
Hours | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
65 | 1 | Humidify Options | 0 | Always humidify regardless of thermostat operating state | |
1 (Default) |
Only humidify when the thermostat operating state is heating, when in heat mode, or when heating in auto mode. When the thermostat is in any other mode, the thermostat will humidify whenever it is necessary. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
7 | 4 | Overshoot | 0 to 30 (Default) |
Overshoot | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
8 | 1 | Heat Staging Delay | 1 to 60 (Default) |
Heat Staging Delay | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
9 | 1 | Cool Staging Delay | 1 to 60 (Default) |
Cool Staging Delay | |