TThere are thousands of interoperable Z-Wave products throughout the world, and over 94 million Z-Wave products have been sold since our beginnings in 2001. All of them work together regardless of brand, because they're all based on the common Z - Wavestandard.Browse our Product Finder to see what Z -Wave can do for you.

Z-Wave Configuration Capabilities

Model: Radio Socket CH (MTSOC-100CH-WL)

Z-Wave Certification Number: ZC10-19056523


Parameter Number

Parameter Size

Parameter Name

Description

1 2 Heartbeat Rate If the Notification System Heartbeat is on, a Notification Report System Heartbeat is sent periodically every 60 minutes (default value).

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

60 1 1440 No No No

From

 

To

Description

1   1440 Heartbeat rate [min]

Parameter Number

Parameter Size

Parameter Name

Description

10 2 Send Interval Humidity If the humidity value does not change, the Multilevel Sensor Report with the actual humidity is sent after the Send Interval Humidity.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 120 No No No

From

 

To

Description

1   120 Send interval humidity [min]

Parameter Number

Parameter Size

Parameter Name

Description

11 2 Minimum Delta Humidity Send Whenever the measured humidity has changed by the Minimum Delta Humidity Send value since the last value sent, the actual humidity is sent by a Multilevel Sensor Report.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

10 10 1000 No No No

From

 

To

Description

10   1000 Minimum delta humidity [0.1 %]

Parameter Number

Parameter Size

Parameter Name

Description

2 2 Main Voltage The Main Voltage is used - together with the Phase Shift parameter and the messured current - to calculate the actual power of the output and the cumulated energy.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

230 80 280 No No No

From

 

To

Description

80   280 Main voltage [V]

Parameter Number

Parameter Size

Parameter Name

Description

3 2 Phase Shift - Cosines (Phi) The Phase Shift is used - together with the Main Voltage parameter and the messured current - to calculate the actual power of the output and the cumulated energy.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

100 0 100 No No No

From

 

To

Description

0   100 Phase shift [0.01%]

Parameter Number

Parameter Size

Parameter Name

Description

4 2 Send Interval Power If the power value of the output does not change, the Meter Report for the actual power is sent after the Send Interval Power.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 120 No No No

From

 

To

Description

1   120 Send interval power [min]

Parameter Number

Parameter Size

Parameter Name

Description

5 2 Minimum Delta Power Send Whenever the calculated power has changed by the Minimum Delta Power Send value since the last value sent, the actual power is sent by a Meter Report.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 100 No No No

From

 

To

Description

1   100 Minimum delta power [%]

Parameter Number

Parameter Size

Parameter Name

Description

7 2 Minimum delta energy send Whenever the cumulated energy has changed by the Minimum Delta Energy send value since the last value sent, the cumulated energy is sent by a Meter Report.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

2000 1 50000 No No No

From

 

To

Description

1   50000 Minimum delta energy [0.001 kWh]

Parameter Number

Parameter Size

Parameter Name

Description

8 2 Send Interval Temperature If the temperature value does not change, the Multilevel Sensor Report with the actual temperature is sent after the Send Interval Temperature

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 120 No No No

From

 

To

Description

1   120 Send interval energy [min]
1   120 Send interval temperature [min]

Parameter Number

Parameter Size

Parameter Name

Description

9 2 Minimum Delta Temperature Send Whenever the measured temperature has changed by the Minimum Delta Temperature Send value since the last value sent, the actual temperature is sent by Multilevel Sensor Report.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 100 No No No

From

 

To

Description

1   100 Minimum delta temperature [0.1 K]