There are over 4252 interoperable
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
1 | 1 | Parameter no. 1 – Input I1 switch type | 0 | push-button (momentary) | |
1 to 0 | on/off toggle switch | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
110 | 2 | Parameter no. 110 – Temperature Sensor Offset Settings | 0 (Default) |
default value 0 | |
-270 to 270 (Default) |
Set value is added to or subtracted from the actually measured value to adjust the temperature report sent by an external sensor. NOTE1: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is -150 – 150 (-15.0 °C – 15.0 °C, resolution 0.1 °C) NOTE2: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is -270 - 270 (-27.0 °F – 27.0 °F, resolution 0.1 °F) NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
120 | 2 | Parameter no. 120 – Temperature Sensor Reporting Threshold | 0 | Reporting disabled | |
0 to 270 (Default) |
This configuration parameters sets reporting threshold between reported temperature and actual temperature for reporting temperature at association group 4. NOTE1: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is 0 – 150 (0 °C – 15.0 °C, resolution 0.1 °C) NOTE2: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 0 - 270 (0 °F – 27.0 °F, resolution 0.1 °F) NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
4 | 1 | Parameter no. 4 – Input 1 contact type | 0 (Default) |
NO (normally open) input type | |
1 to 0 | NC (normally close) input type | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
40 | 1 | Parameter no. 40 – Watt Power Consumption Reporting Threshold for Q⬆ Load | 0 | Power consumption reporting disabled | |
1 to 100 (Default) |
1% - 100% Power consumption reporting enabled. New value is reported only when Wattage in real time changes by more than the percentage value set in this parameter compared to the previous Wattage reading, starting at 1% (the lowest value possible). | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
42 | 2 | Parameter no. 42 – Watt Power Consumption Reporting Time Threshold for Q⬆ | 0 | Power consumption reporting disabled | |
30 to 32767 (Default) |
30 - 32767 = 30 - 32767 seconds. Power consumption reporting enabled. Report is sent according to time interval (value) set here. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
43 | 2 | Parameter no. 43 – Hysteresis Upper temperature offset | 0 to 450 (Default) |
This parameter defines minimum temperature difference between real measured temperature and set-point temperature to turn device on in heat mode or turn device off in cool mode. NOTE1: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is 0 – 250 (0.0 °C – 25.0 °C, resolution 0.1 °C) NOTE2: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 0 – 450 (0.0 °F – 45.0 °F, resolution 0.1 °F) NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth. | |
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
44 | 2 | Parameter no. 44 – Hysteresis Lower temperature offset | 0 to 450 (Default) |
||
0 to 450 (Default) |
This parameter defines minimum temperature difference between real measured temperature and set-point temperature to turn device off in heat mode or turn device on in cool mode. NOTE1: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is 0 – 250 (0.0 °C – 25.0 °C, resolution 0.1 °C) NOTE2: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 0 – 450 (0.0 °F – 45.0 °F, resolution 0.1 °F) NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
45 | 2 | Parameter no. 45 – Antifreeze | 0 | default value 50 (5.0 Celsius) | |
-125 to 545 (Default) |
Set value determines at which temperature the device will be turned on even (if the thermostat was manually set to off). NOTE1: Antifreeze is activated only in heating mode and it uses hysteresis of ±0.5°C. NOTE2: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is -125 – 125 (-12.5 °C – 12.5 °C, resolution 0.1 °C) NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 95 – 545 (9.5 °F – 54.5 °F, resolution 0.1 °F) NOTE4: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth. | ||||
1000 to 0 | Antifreeze functionality disabled. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
59 | 1 | Parameter no. 59 - Thermostat mode | 0 (Default) |
Heat mode | |
1 to 0 | Cool mode | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
60 | 2 | Parameter no. 60 – Too low temperature limit | 0 | Default value 50 (Too low temperature limit is 5.0 Celsius) | |
-150 to 2120 (Default) |
This parameter determines the temperature at which the device sends a command to the associated device - to turn ON device or to turn OFF device. NOTE1: Too low temperature limit is used with Association Group 3. NOTE2: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is -150 – 1000 (-15.0 °C – 100.0 °C, resolution 0.1 °C) NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 50 – 2120 (5.0 °F – 212.0 °F, resolution 0.1 °F) NOTE4: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
61 | 2 | Parameter no. 61 – Too high temperature limit | 0 | default value 700 (too high temperature limit is 70.0 Celsius) | |
1 to 2120 (Default) |
This parameter determines the temperature at which the device sends a command to the associated device, to turn ON device or to turn OFF device. NOTE1: Too high temperature limit is used with Association Group 3. NOTE2: If configuration parameter 78 (Scale selection) is set to Celsius, then valid interval is 1 – 1000 (0.1 °C – 100.0 °C, resolution 0.1 °C) NOTE3: If configuration parameter 78 (Scale selection) is set to Fahrenheit, then valid interval is 322 – 2120 (32.2 °F – 212.0 °F, resolution 0.1 °F) NOTE4: If configuration parameter 78 (Scale selection) is set to Fahrenheit, note that Fahrenheit values will be converted to Celsius degrees. Due to conversion algorithm please be advised that configuration value could drift when converting values back and forth. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
63 | 1 | Parameter no. 63 – Output switch selection | 0 (Default) |
When switch/device is off the output is 0V (NC) | |
1 to 0 | When switch/device is off the output is 240V or 24V (NO). | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Parameter Values |
||
78 | 1 | Parameter no. 78 – Scale Selection | 0 (Default) |
0 = degrees Celsius | |
1 to 0 | 1 = degrees Fahrenheit | ||||