There are over 4393 interoperable Z-Wave products throughout the world, and over 94 million Z-Wave products have been sold since our beginnings in 2001. All of them work together regardless of brand, because they're all based on the common Z - Wavestandard.Browse our Product Finder to see what Z -Wave can do for you.

Z-Wave Configuration Capabilities

Model: Fan Coil Thermostat (HE-FT01)

Z-Wave Certification Number: ZC12-20010025


Parameter Number

Parameter Size

Parameter Name

Description

1 1 TIME CORRECTION Time correction by controller

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

1 0 1 No No No

Bit (Value)

 

Description

0 (1)   Switch off auto-correction
1 (2)   If thermostat is connected to a Z-Wave gateway, the time and day will be periodically polled and corrected from the gateway

Parameter Number

Parameter Size

Parameter Name

Description

10 1 MANUAL BRIGHTNESS Display manual brightness level. The Display Brightness Level Parameter will take effect when Parameter 22 is set to Manual Control (value = 0). Note: The environment illumination is displayed in the TIME position and also can be checked at any time via a Z-Wave gateway.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

10 1 15 No No No

Value

 

Description

1   The LCD brightness may be adjusted from 1 (lowest brightness) to 15 (highest brightest).

Parameter Number

Parameter Size

Parameter Name

Description

11 1 TOUCH THRESHOLD Touch buttons sensitivity. 5 = Highly sensitive. 50 = Lowest sensitivity. Note: Setting the sensitivity too high can lead to false touch detection. We recommend not changing this Parameter unless there is a need to do so.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

15 5 50 No No No

Value

 

Description

5   Threshold to be adjusted from level 5 (very sensitive) to 50 (minimal sensitivity).

Parameter Number

Parameter Size

Parameter Name

Description

12 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

13 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

14 1 BASIC SET MODE Mode to switch to on Basic Set Action command This Parameter defines which Operating Mode the HE-FT01 reverts to if the Basic Set command is received. If the Basic Set command value is 0 (OFF state) the HE-FT01 will go to OFF mode and switch the operating state to IDLE. If the Basic Set command value is 0xFF (ON state) the HE-FT01 will change the Mode to the corresponding Parameter value.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

2 0 9 No No No

Bit (Value)

 

Description

0 (1)   No action
1 (2)   COM with Heating & Cooling Climate Mode
2 (4)   COM with Heating Climate Mode
3 (8)   COM with Cooling Climate Mode
4 (16)   TIME with Heating & Cooling Climate Mode
5 (32)   TIME with Heating Climate Mode
6 (64)   TIME with Cooling Climate Mode
7 (128)   ECO with Heating Climate Mode
8 (256)   ECO with Cooling Climate Mode
9 (512)   Ventilation Climate Mode

Parameter Number

Parameter Size

Parameter Name

Description

15 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

16 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

17 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

18 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

19 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

2 1 TIME FORMAT Time format

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

1 0 1 No No No

Bit (Value)

 

Description

0 (1)   24 hour format
1 (2)   12 hour (AM/PM) format

Parameter Number

Parameter Size

Parameter Name

Description

20 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

21 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

22 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

23 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

24 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

25 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

26 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

27 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

28 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

29 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

3 1 WEEKDAY Week day. This parameter allows manually adjustment of the day of the week in case if the thermostat is not connected to any Z-Wave gateway or Parameter 09 (auto-correction) is selected as 0.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

1 1 7 No No No

Bit (Value)

 

Description

1 (2)   Monday
2 (4)   Tuesday
3 (8)   Wednesday
4 (16)   Thursday
5 (32)   Friday
6 (64)   Saturday
7 (128)   Sunday

Parameter Number

Parameter Size

Parameter Name

Description

30 1 RESERVED Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality.

Parameter Number

Parameter Size

Parameter Name

Description

31 1 SENSORS REPORT TIME Sensors consecutive reporting interval, minutes. When the device is connected to the Z-Wave gateway (controller), it periodically sends to the gateway reports from its room & floor temperature, humidity and light sensors even if there are not changes in the values. This Parameter defines the interval between consecutive reports. The value can be adjusted from 1 min to 120 min. Note: If the sensor readings change, the device will send the report to the gateway regardless of this parameter value. In order not to increase traffic on your network, it is not recommended to reduce the value of this parameter. We recommend to reduce the value of this parameter only in case of poor connection, when reports from the device does not always reach the gateway.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

10 1 120 No No No

Value

 

Description

1   The value can be adjusted from 1 to 120 minutes

Parameter Number

Parameter Size

Parameter Name

Description

32 1 CONSUMPTION REPORT TIME This Parameter defines the interval (in minutes) between consecutive reports of real time and cumulative energy consumption data to the gateway. The value can be adjusted from 1 min to 120 min. The factory default value is 10 min. Note: If the sensor readings change, the device will send the report to the gateway regardless of this parameter value. In order to not increase traffic on your network, we recommend not reducing this value.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

10 1 120 No No No

Value

 

Description

1   Consumption meter consecutive reporting interval in minutes.

Parameter Number

Parameter Size

Parameter Name

Description

33 1 TEMPERATURE THRESHOLD Temperature difference to send to controller, value x10. This parameter determines the change in temperature level (in °C) resulting in temperature sensors report being sent to the gateway. The value of this parameter should be x10, e.g. for 0.4°C use value 40. From 0.5°C to 10°C can be selected. The factory default value is 0.5°C (5).

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 0 100 No No No

Value

 

Description

0   Stop sending the reports
5   Temperature level difference (in °C), value x10.

Parameter Number

Parameter Size

Parameter Name

Description

34 1 HUMIDITY THRESHOLD This parameter determines the percentage change in relative humidity level which will trigger a report being sent to the gateway. From 2% to 25% can be selected.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

2 0 25 No No No

Value

 

Description

0   Stop sending the reports
2   Humidity level difference in %

Parameter Number

Parameter Size

Parameter Name

Description

35 1 LIGHT THRESHOLD This parameter determines the change in the ambient illumination level that will trigger a report being sent to the gateway.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

50 0 99 No No No

Value

 

Description

0   Stop sending the reports
10   Light sensor values difference

Parameter Number

Parameter Size

Parameter Name

Description

36 2 OUT–1 LOAD Power of the Relay 1 load in W. It is possible to specify the consumption of the loads in watts for each relays channel. The device will calculate total consumption relative to the time, during which the output of the relays is in the ON state.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 5000 No No No

Value

 

Description

0   Power of the Relay 1 load in W

Parameter Number

Parameter Size

Parameter Name

Description

37 2 OUT-2 LOAD Power of the Relay 2 load in W. It is possible to specify the consumption of the loads in watts for each relays channel. The device will calculate total consumption relative to the time, during which the output of the relays is in the ON state.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 5000 No No No

Value

 

Description

0   Power of the Relay 2 load in W

Parameter Number

Parameter Size

Parameter Name

Description

38 2 OUT–3 LOAD Power of the Relay 3 load in W. It is possible to specify the consumption of the loads in watts for each relays channel. The device will calculate total consumption relative to the time, during which the output of the relays is in the ON state.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 5000 No No No

Value

 

Description

0   Power of the Relay 3 load in W

Parameter Number

Parameter Size

Parameter Name

Description

39 2 OUT–4 LOAD Power of the Relay 4 load in W. It is possible to specify the consumption of the loads in watts for each relays channel. The device will calculate total consumption relative to the time, during which the output of the relays is in the ON state.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 5000 No No No

Value

 

Description

0   Power of the Relay 4 load in W

Parameter Number

Parameter Size

Parameter Name

Description

4 1 HOUR This Parameter allows manual adjustment of Time in hours (24 hours).

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 23 No No No

Value

 

Description

0   Manual adjustment of time hours (24 hours).

Parameter Number

Parameter Size

Parameter Name

Description

40 2 OUT–5 LOAD Power of the Relay 5 load in W. It is possible to specify the consumption of the loads in watts for each relays channel. The device will calculate total consumption relative to the time, during which the output of the relays is in the ON state.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 5000 No No No

Value

 

Description

0   Power of the Relay 5 load in W

Parameter Number

Parameter Size

Parameter Name

Description

41 1 TIME MODE OPERATION This parameter determines the Climate Mode (Heating or Cooling) to which HE-FT01 will switch when the TIME operating mode is selected.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

1 1 3 No No No

Bit (Value)

 

Description

1 (2)   The thermostat will go to Heating & Cooling mode
2 (4)   The thermostat goes to Heating mode
3 (8)   The thermostat goes to Cooling Mode

Parameter Number

Parameter Size

Parameter Name

Description

42 2 MORNING START TIME Morning start time for the Temperature Schedules. Format: HHMM. e.g.08:00 should be sent as 0800.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

600 0 2359 No No No

Value

 

Description

0   Morning start time. Format: HHMM (from 00:00 to 23:59)

Parameter Number

Parameter Size

Parameter Name

Description

43 2 DAY START TIME Day start time for the Temperature Schedules. Format: HHMM. e.g.08:00 should be sent as 0800.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

900 0 2359 No No No

Value

 

Description

0   Day start time. Format: HHMM (from 00:00 to 23:59)

Parameter Number

Parameter Size

Parameter Name

Description

44 2 EVENING START TIME Evening start time for the Temperature Schedules. Format: HHMM. e.g.08:00 should be sent as 0800.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

1800 0 2359 No No No

Value

 

Description

0   Evening start time. Format: HHMM (from 00:00 to 23:59)

Parameter Number

Parameter Size

Parameter Name

Description

45 2 NIGHT START TIME Night start time for the Temperature Schedules. Format: HHMM. e.g.08:00 should be sent as 0800.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

2300 0 2359 No No No

Value

 

Description

0   Night start time. Format: HHMM (from 00:00 to 23:59)

Parameter Number

Parameter Size

Parameter Name

Description

46 2 MONDAY MORNING TEMP Monday Morning temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

240 40 370 No No No

Value

 

Description

40   Monday Morning temperature value

Parameter Number

Parameter Size

Parameter Name

Description

47 2 MONDAY DAYTIME TEMP Monday Day temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

200 40 370 No No No

Value

 

Description

40   Monday Day temperature value

Parameter Number

Parameter Size

Parameter Name

Description

48 2 MONDAY EVENING TEMP Monday Evening temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

230 40 370 No No No

Value

 

Description

40   Monday Evening temperature value

Parameter Number

Parameter Size

Parameter Name

Description

49 2 MONDAY NIGHT TEMP Monday Night temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

180 40 370 No No No

Value

 

Description

40   Monday Night temperature value

Parameter Number

Parameter Size

Parameter Name

Description

5 1 MINUTE This Parameter allows manual adjustment of the Time in minutes (60 minutes))

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 59 No No No

Value

 

Description

0   Manual adjustment of time minutes (60 minutes)

Parameter Number

Parameter Size

Parameter Name

Description

50 2 TUESDAY MORNING TEMP Tuesday Morning temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

240 40 370 No No No

Value

 

Description

40   Tuesday Morning temperature value

Parameter Number

Parameter Size

Parameter Name

Description

51 2 TUESDAY DAYTIME TEMP Tuesday Day temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

200 40 370 No No No

Value

 

Description

40   Tuesday Day temperature value

Parameter Number

Parameter Size

Parameter Name

Description

52 2 TUESDAY EVENING TEMP Tuesday Evening temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

230 40 370 No No No

Value

 

Description

40   Tuesday Evening temperature value

Parameter Number

Parameter Size

Parameter Name

Description

53 2 TUESDAY NIGHT TEMP Tuesday Night temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

180 40 370 No No No

Value

 

Description

40   Tuesday Night temperature value

Parameter Number

Parameter Size

Parameter Name

Description

54 2 WEDNESDAY MORNING TEMP Wednesday Morning temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

240 40 370 No No No

Value

 

Description

40   Wednesday Morning temperature value

Parameter Number

Parameter Size

Parameter Name

Description

55 2 WEDNESDAY DAYTIME TEMP Wednesday Day temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

200 40 370 No No No

Value

 

Description

40   Wednesday Day temperature value

Parameter Number

Parameter Size

Parameter Name

Description

56 2 WEDNESDAY EVENING TEMP Wednesday Evening temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

230 40 370 No No No

Value

 

Description

40   Wednesday Evening temperature value

Parameter Number

Parameter Size

Parameter Name

Description

57 2 WEDNESDAY NIGHT TEMP Wednesday Night temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

180 40 370 No No No

Value

 

Description

40   Wednesday Night temperature value

Parameter Number

Parameter Size

Parameter Name

Description

58 2 THURSDAY MORNING TEMP Thursday Morning temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

240 40 370 No No No

Value

 

Description

40   Thursday Morning temperature value

Parameter Number

Parameter Size

Parameter Name

Description

59 2 THURSDAY DAYTIME TEMP Thursday Day temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

200 40 370 No No No

Value

 

Description

40   Thursday Day temperature value

Parameter Number

Parameter Size

Parameter Name

Description

6 1 DEGREE MODE Degree mode (C/F) Floor and air temperature, as well as Set Point and all Parameters will be indicated in the chosen mode. Factory default value is degrees Celsius (0).

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Bit (Value)

 

Description

0 (1)   Celsius
1 (2)   Fahrenheit

Parameter Number

Parameter Size

Parameter Name

Description

60 2 THURSDAY EVENING TEMP Thursday Evening temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

230 40 370 No No No

Value

 

Description

40   Thursday Evening temperature value

Parameter Number

Parameter Size

Parameter Name

Description

61 2 THURSDAY NIGHT TEMP Thursday Night temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

180 40 370 No No No

Value

 

Description

40   Thursday Night temperature value

Parameter Number

Parameter Size

Parameter Name

Description

62 2 FRIDAY MORNING TEMP Friday Morning temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

240 40 370 No No No

Value

 

Description

40   Friday Morning temperature value

Parameter Number

Parameter Size

Parameter Name

Description

63 2 FRIDAY DAYTIME TEMP Friday Day temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

200 40 370 No No No

Value

 

Description

40   Friday Day temperature value

Parameter Number

Parameter Size

Parameter Name

Description

64 2 FRIDAY EVENING TEMP Friday Evening temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

230 40 370 No No No

Value

 

Description

40   Friday Evening temperature value

Parameter Number

Parameter Size

Parameter Name

Description

65 2 FRIDAY NIGHT TEMP Friday Night temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

180 40 370 No No No

Value

 

Description

40   Friday Night temperature value

Parameter Number

Parameter Size

Parameter Name

Description

66 2 SATURDAY MORNING TEMP Saturday Morning temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

240 40 370 No No No

Value

 

Description

40   Saturday Morning temperature value

Parameter Number

Parameter Size

Parameter Name

Description

67 2 SATURDAY DAYTIME TEMP Saturday Day temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

200 40 370 No No No

Value

 

Description

40   Saturday Day temperature value

Parameter Number

Parameter Size

Parameter Name

Description

68 2 SATURDAY EVENING TEMP Saturday Evening temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

230 40 370 No No No

Value

 

Description

40   Saturday Evening temperature value

Parameter Number

Parameter Size

Parameter Name

Description

69 2 SATURDAY NIGHT TEMP Saturday Night temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

180 40 370 No No No

Value

 

Description

40   Saturday Night temperature value

Parameter Number

Parameter Size

Parameter Name

Description

7 1 AIR TEMP CORRECTION This Parameter defines the offset value for room air temperature. If the internal air temperature sensor is not correctly calibrated, then manual calibration can be accomplished by adjusting the values up to ±9.5°C (±17°F). This value will be added or subtracted from the internal air temperature sensor reading.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 -95 95 No No No

From

 

To

Description

-95   95 Air temperature offset value (°C x 10)

Parameter Number

Parameter Size

Parameter Name

Description

70 2 SUNDAY MORNING TEMP Sunday Morning temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

240 40 370 No No No

Value

 

Description

40   Sunday Morning temperature value

Parameter Number

Parameter Size

Parameter Name

Description

71 2 SUNDAY DAYTIME TEMP Sunday Day temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

200 40 370 No No No

Value

 

Description

40   Sunday Day temperature value

Parameter Number

Parameter Size

Parameter Name

Description

72 2 SUNDAY EVENING TEMP Sunday Evening temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

230 40 370 No No No

Value

 

Description

40   Sunday Evening temperature value

Parameter Number

Parameter Size

Parameter Name

Description

73 2 SUNDAY NIGHT TEMP Sunday Night temperature, valueX10

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

180 40 370 No No No

Value

 

Description

40   Sunday Night temperature value

Parameter Number

Parameter Size

Parameter Name

Description

8 1 TEMP HYSTERESYS This Parameter defines the hysteresis value for temperature control. The HE-FT01 will stabilize the temperature with the selected hysteresis. For example, if the SET POINT is set for 25°C and HYSTERESIS is set for 0.5°C, the HE-FT01 will change the state to IDLE if the temperature reaches 25.0°C. It will change the state to HEATING if the temperature becomes lower than 24.5°C, and will change the state to COOLING if the temperature rises beyond 25.5°C. The hysteresis value can be changed from 0.2°C to 10.0°C range in Celsius mode, and 0.3°F to 18.0°F in Fahrenheit. The factory-default value is 0.5°C (0.9°F).

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 2 100 No No No

Value

 

Description

2   Temperature hysteresis value (°C x 10)

Parameter Number

Parameter Size

Parameter Name

Description

9 1 AUTO BRIGHTNESS Display auto-brightness control The HE-FT01 can adjust its display brightness automatically depending on the ambient room brightness.

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

1 0 1 No No No

Bit (Value)

 

Description

0 (1)   Manual Control: Inactive Level brightness will be set to the level defined by Parameter 10.
1 (2)   Automatic Brightness Control.