There are over 4393 interoperable
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
1 | 1 | DEVICE TYPE | Device Type. This parameter is read only and indicates in which mode the device is included. The device can be included either in the Binary Switch mode or in the Thermostat mode. Use inclusion in Binary Switch mode if there is a need to control on/off device and use inclusion in Thermostat mode if there is a need to control heating system. For the appropriate inclusion process see the section Z-Wave Network of manual. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | Parameter is read only. | ||||
1 (2) | Parameter is read only. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
10 | 1 | TEMPERATURE SCALE MODE | Temperature Scale Mode. This parameter determines in which unit of measurement (degrees Celsius or Fahrenheit) the device will report the temperature, and also determines the scale that will be interpreted by the configuration parameters. Note: This configuration parameter has impact on configuration parameters 9,12,16,17 and 32, 42-69 in thermostat mode. If scale is set to degrees Fahrenheit, configuration values at mentioned parameters will be automatically converted from Celsius to Fahrenheit and any change in the values will be interpreted as Fahrenheits. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | Celsius | ||||
1 (2) | Fahrenheit | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
11 | 1 | TEMPERATURE REPORT INTERVAL | Temperature Sensor Consecutive Report Interval. This Parameter defines the interval between consecutive reports of temperature sensor reading to the gateway. Note: If the sensor readings change, the device will send the report to the gateway regardless of this parameter value. In order not to increase traffic on your network, it is not recommended to reduce the value of this parameter. We recommend reducing the value of this parameter only in case of poor connection, when reports from the device does not always reach the gateway. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
10 | 1 | 120 | No | No | No |
Value |
Description |
||||
1 | The value can be adjusted from 1 to 120 minutes | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
12 | 1 | TEMPERATURE REPORT THRESHOLD | Temperature Sensor Report Threshold. This parameter determines the change in temperature level resulting in temperature sensors report being sent to the gateway. In Celsius scale mode the value of this parameter should be x10, e.g. for 0.4°C use value 4. From 1 (0.1°C) to 100 (10°C) can be selected in Celsius scale mode and from 1 to 18 can be selected in Fahrenheit scale mode. The factory default value is 5 (0.5°) in °C scale and 1 in °F scale. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
5 | 0 | 100 | No | No | No |
Value |
Description |
||||
0 | Stop sending the reports | ||||
1 | The change in temperature level resulting in temperature sensors report being sent to the gateway. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
13 | 1 | METER REPORT INTERVAL | Energy Consumption Meter Consecutive Report Interval. When the device is connected to the Z-Wave gateway (controller), it periodically sends to the gateway reports from its external temperature sensor and energy consumption meter even if there are not changes in the values. This Parameter defines the interval between consecutive reports of real time and cumulative energy consumption data to the gateway. Note: If the sensor readings change, the device will send the report to the gateway regardless of this parameter value. In order not to increase traffic on your network, it is not recommended to reduce the value of this parameter. We recommend reducing the value of this parameter only in case of poor connection, when reports from the device does not always reach the gateway. Note: Energy consumption meter function is available only if the device is AC powered. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
10 | 1 | 120 | No | No | No |
Value |
Description |
||||
1 | The value can be adjusted from 1 to 120 minutes. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
131 | 1 | LOAD ON NOTIFICATION | The actual parameter number is 31 when the device is in the 'Binary Switch' mode. Load Switched On Notification. If this function is enabled the device will send “AC Mains Re-Connected” notification to the gateway each time when the relay output state changes to On. Note: This function can be useful for informing in case of automatic control of the load by schedule or scenario. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | Disable sending the notification | ||||
1 (2) | Enable sending the notification | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
132 | 1 | LOAD OFF NOTIFICATION | The actual parameter number is 32 when the device is in the 'Binary Switch' mode. Load Switched Off Notification. If this function is enabled the device will send “AC Mains Disconnected” notification to the gateway each time when the relay output state changes to Off. Note: This function can be useful for informing when the device automatically switches the output Off because of emergency case or in case of automatic control of the load by schedule or scenario. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
1 | 0 | 1 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | Disable sending the notification | ||||
1 (2) | Enable sending the notification | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
133 | 2 | TIME LIMITITED LOAD | The actual parameter number is 33 when the device is in the 'Binary Switch' mode. High Load Timeout Protection: Power Threshold If the HLS01 is used to control an electric socket, you can configure the device so that it automatically switch Off the socket if the potentially dangerous high load is connected longer than allowable time (time to be set in the Parameter 34), for example, if you left the iron switched On for too long. Set in this parameter the threshold value in watts, reaching which the connected load will be considered high. Note: If the connected load power is less than value of this parameter, the protection will not be activated. Note: If the Parameter 34 (time threshold) value is set to 0, the protection will not be activated. Note: The time counter is reset every time when the load consumption drops to zero. Note: We recommend activating the Load Switched Off notification (the Parameter 32) to be informed when the device automatically switch Off the socket. Note: The protection works only if the device is AC powered. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 3500 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
100 | The load limit in watts to automatically switch Off the socket | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
134 | 2 | HIGH LOAD ON TIME LIMIT | The actual parameter number is 34 when the device is in the 'Binary Switch' mode. High Load Timeout Protection: Time Threshold If High Load Timeout Protection is activated (the Parameter 33 is set) use this parameter to set the threshold value in minutes. If the load is connected longer than this value, the device will automatically switch Off the socket. Note: If the value of this parameter is set 0, the protection will not be activated. Note: If the connected load power is less than value of the Parameter 33, the protection will not be activated. Note: The time counter is reset every time when the load consumption drops to zero. If the connected load may change its consumption, make sure that the time threshold will be reached before the load consumption drops. Note: We recommend activating the Load Switched Off notification (the Parameter 32) to be informed when the device automatically switch Off the socket. Note: The protection works only if the device is AC powered. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1440 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
1 | If the load is connected longer than this value, the device will automatically switch Off the socket. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
135 | 1 | LOAD AUTO ON/OFF | The actual parameter number is 35 when the device is in the 'Binary Switch' mode. Load Switched On Notification. Auto On/Off If this function is enabled the device will switch Off the relay output when there is no consumption and switch On the output again when the load is reconnected. It is possible to set the delay for Auto Off function (in the Parameter 36) and for Auto On function (in the Parameter 37). Note: If the output is manually switched Off (from Gateway or External Input toggle) Auto ON function will be blocked until the output switches back to ON manually or the load disconnected. Note: The function works only if the device is AC powered. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | Disable the functionality | ||||
1 (2) | Enable the functionality | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
136 | 1 | AUTO OFF TIMEOUT | The actual parameter number is 36 when the device is in the 'Binary Switch' mode. Load Switched On Notification. Auto Off Timeout If Auto On/Off function (the Parameter 35) is enabled, it is possible to delay the Auto Off function. The output will be switched Off when there is no consumption for the interval defined in this parameter in minutes. Note: The function works only if the device is AC powered. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
5 | 0 | 120 | No | No | No |
Value |
Description |
||||
0 | Switch Off the output immediately when consumption drops to 0W | ||||
1 | Minutes after which the output will be switched Off when there is no consumption | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
137 | 1 | AUTO ON RECONNECT TIMEOUT | The actual parameter number is 37 when the device is in the 'Binary Switch' mode. Load Switched On Notification. Auto On Reconnect Timeout If Auto On/Off function (the Parameter 35) is enabled, it is possible to delay the Auto On function. When the load is reconnected the relay output will be switched On after the time defined in this parameter in minutes. Note: The function works only if the device is AC powered. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 120 | No | No | No |
Value |
Description |
||||
0 | Switch On the output immediately when the load is reconnected. | ||||
1 | When the load is reconnected the relay output will be switched On after the time defined in this parameter in minutes. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
138 | 1 | S1 INPUT HOLD CONTROL MODE | The actual parameter number is 38 when the device is in the 'Binary Switch' mode. Load Switched On Notification. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
2 | 0 | 3 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | Hold function is disabled | ||||
1 (2) | Operate like click (the Parameter 39) | ||||
2 (4) | Momentary Switch: When the button on switch connected to external input is held, (key closed) the relay output state is ON, as soon as the button is released (key opened) the relay output state changes to OFF. | ||||
3 (8) | Reversed Momentary Switch: When the button on switch connected to external input is held, the relay output state is OFF, as soon as the button is released the relay output state changes to ON. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
139 | 1 | S1 INPUT CLICK CONTROL MODE | The actual parameter number is 39 when the device is in the 'Binary Switch' mode. External Input: Click Control Mode. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
1 | 0 | 5 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | Click function disabled | ||||
1 (2) | Toggle switch: relay inverts state (ON to OFF, OFF to ON). | ||||
2 (4) | Relay switches to ON state only | ||||
3 (8) | Relay switches to OFF state only | ||||
4 (16) | Timer: On>Off Mode: Relay output switches to ON state (contacts are closed) then after a specified time switches back to OFF state (contacts are open). The time is specified in the Parameter 40. | ||||
5 (32) | Timer: OFF>ON Mode: Relay output switches to OFF state (contacts are open) then after a specified time switches back to ON state (contacts are closed). The time is specified in Parameter 40. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
14 | 1 | METER REPORT THRESHOLD | Energy Consumption Meter Report Threshold. This parameter determines how much the cumulative or real time energy consumption data need to increase/reduce to be reported to the gateway. The value of this parameter is in % and from 1 to 90 can be selected. Note: Energy consumption meter function is available only if the device is AC powered. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
25 | 0 | 90 | No | No | No |
Value |
Description |
||||
0 | Stop sending the reports | ||||
1 | The percentage (%) change in ambient illumination that results in cumulative or real time energy consumption data being sent to the gateway. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
140 | 2 | RELAY TIMER DURATION | The actual parameter number is 40 when the device is in the 'Binary Switch' mode. Relay Timer Mode Duration These parameters specify the duration in seconds for the Timer mode (values 4 or 5 in the Parameter 39). Press the button on the switch connected to external input and the relay output goes to ON/OFF for the specified time then changes back to OFF/ON. Note: If the parameter value is set to “0” the relay output will operate as a short contact (duration is about 0.5 sec). | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 43200 | No | No | No |
Value |
Description |
||||
0 | The time value can be configured from 0 sec to 43200 sec (12 hours). | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
141 | 4 | RELAY CONTROL SCENARIO 1 | The actual parameter number is 41 when the device is in the 'Binary Switch' mode. Relay 1 Control by Scenario In these parameters, the relay state changes depending on day and time. For these configurations, parameter values are encoded as 7-digit numbers (ABCDEFG). A: State. 0 = Disabled, 1 = Enabled B: Day of week 0 = every day 1-7 = corresponding day (1 is Monday, 7 is Sunday) 8 = every weekday (Monday - Friday) 9 = every weekend (Saturday and Sunday) C: Change state to 0 = Switch OFF 1 = Switch ON DEFG: Time DE represents Hour (from 0 to 23), FG represents Minutes (from 0 to 59). | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1912359 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
1000000 | Relay 1 Control Scenario | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
142 | 4 | RELAY CONTROL SCENARIO 2 | The actual parameter number is 42 when the device is in the 'Binary Switch' mode. Relay 2 Control by Scenario In these parameters, the relay state changes depending on day and time. For these configurations, parameter values are encoded as 7-digit numbers (ABCDEFG). A: State. 0 = Disabled, 1 = Enabled B: Day of week 0 = every day 1-7 = corresponding day (1 is Monday, 7 is Sunday) 8 = every weekday (Monday - Friday) 9 = every weekend (Saturday and Sunday) C: Change state to 0 = Switch OFF 1 = Switch ON DEFG: Time DE represents Hour (from 0 to 23), FG represents Minutes (from 0 to 59). | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1912359 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
1000000 | Relay 2 Control Scenario | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
143 | 4 | RELAY CONTROL SCENARIO 3 | The actual parameter number is 43 when the device is in the 'Binary Switch' mode. Relay 3 Control by Scenario In these parameters, the relay state changes depending on day and time. For these configurations, parameter values are encoded as 7-digit numbers (ABCDEFG). A: State. 0 = Disabled, 1 = Enabled B: Day of week 0 = every day 1-7 = corresponding day (1 is Monday, 7 is Sunday) 8 = every weekday (Monday - Friday) 9 = every weekend (Saturday and Sunday) C: Change state to 0 = Switch OFF 1 = Switch ON DEFG: Time DE represents Hour (from 0 to 23), FG represents Minutes (from 0 to 59). | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1912359 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
1000000 | Relay 3 Control Scenario | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
144 | 4 | RELAY CONTROL SCENARIO 4 | The actual parameter number is 44 when the device is in the 'Binary Switch' mode. Relay 4 Control by Scenario In these parameters, the relay state changes depending on day and time. For these configurations, parameter values are encoded as 7-digit numbers (ABCDEFG). A: State. 0 = Disabled, 1 = Enabled B: Day of week 0 = every day 1-7 = corresponding day (1 is Monday, 7 is Sunday) 8 = every weekday (Monday - Friday) 9 = every weekend (Saturday and Sunday) C: Change state to 0 = Switch OFF 1 = Switch ON DEFG: Time DE represents Hour (from 0 to 23), FG represents Minutes (from 0 to 59). | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1912359 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
1000000 | Relay 4 Control Scenario | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
145 | 4 | RELAY CONTROL SCENARIO 5 | The actual parameter number is 45 when the device is in the 'Binary Switch' mode. Relay 5 Control by Scenario In these parameters, the relay state changes depending on day and time. For these configurations, parameter values are encoded as 7-digit numbers (ABCDEFG). A: State. 0 = Disabled, 1 = Enabled B: Day of week 0 = every day 1-7 = corresponding day (1 is Monday, 7 is Sunday) 8 = every weekday (Monday - Friday) 9 = every weekend (Saturday and Sunday) C: Change state to 0 = Switch OFF 1 = Switch ON DEFG: Time DE represents Hour (from 0 to 23), FG represents Minutes (from 0 to 59). | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1912359 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
1000000 | Relay 5 Control Scenario | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
146 | 4 | RELAY CONTROL SCENARIO 6 | The actual parameter number is 46 when the device is in the 'Binary Switch' mode. Relay 6 Control by Scenario In these parameters, the relay state changes depending on day and time. For these configurations, parameter values are encoded as 7-digit numbers (ABCDEFG). A: State. 0 = Disabled, 1 = Enabled B: Day of week 0 = every day 1-7 = corresponding day (1 is Monday, 7 is Sunday) 8 = every weekday (Monday - Friday) 9 = every weekend (Saturday and Sunday) C: Change state to 0 = Switch OFF 1 = Switch ON DEFG: Time DE represents Hour (from 0 to 23), FG represents Minutes (from 0 to 59). | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1912359 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
1000000 | Relay 6 Control Scenario | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
147 | 4 | RELAY CONTROL SCENARIO 7 | The actual parameter number is 47 when the device is in the 'Binary Switch' mode. Relay 7 Control by Scenario In these parameters, the relay state changes depending on day and time. For these configurations, parameter values are encoded as 7-digit numbers (ABCDEFG). A: State. 0 = Disabled, 1 = Enabled B: Day of week 0 = every day 1-7 = corresponding day (1 is Monday, 7 is Sunday) 8 = every weekday (Monday - Friday) 9 = every weekend (Saturday and Sunday) C: Change state to 0 = Switch OFF 1 = Switch ON DEFG: Time DE represents Hour (from 0 to 23), FG represents Minutes (from 0 to 59). | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1912359 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
1000000 | Relay 7 Control Scenario | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
148 | 4 | RELAY CONTROL SCENARIO 8 | The actual parameter number is 48 when the device is in the 'Binary Switch' mode. Relay 8 Control by Scenario In these parameters, the relay state changes depending on day and time. For these configurations, parameter values are encoded as 7-digit numbers (ABCDEFG). A: State. 0 = Disabled, 1 = Enabled B: Day of week 0 = every day 1-7 = corresponding day (1 is Monday, 7 is Sunday) 8 = every weekday (Monday - Friday) 9 = every weekend (Saturday and Sunday) C: Change state to 0 = Switch OFF 1 = Switch ON DEFG: Time DE represents Hour (from 0 to 23), FG represents Minutes (from 0 to 59). | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1912359 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
1000000 | Relay 8 Control Scenario | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
149 | 4 | RELAY CONTROL SCENARIO 9 | The actual parameter number is 49 when the device is in the 'Binary Switch' mode. Relay 9 Control by Scenario In these parameters, the relay state changes depending on day and time. For these configurations, parameter values are encoded as 7-digit numbers (ABCDEFG). A: State. 0 = Disabled, 1 = Enabled B: Day of week 0 = every day 1-7 = corresponding day (1 is Monday, 7 is Sunday) 8 = every weekday (Monday - Friday) 9 = every weekend (Saturday and Sunday) C: Change state to 0 = Switch OFF 1 = Switch ON DEFG: Time DE represents Hour (from 0 to 23), FG represents Minutes (from 0 to 59). | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1912359 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
1000000 | Relay 9 Control Scenario | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
15 | 1 | SYSTEM ERROR NOTIFICATION | Device Failure Notifications. If the HLS01 does not work properly it sends “System Failure” notification to the gateway with the error code. Errors code list (sent with the notification): 0 – No Error (no issue is detected) 1 – Relay Off Error (when unable to switch Off the relay output). 2 – Relay On Error (when unable to switch On the relay output). 3 – Relay On & Off Error (when unable to switch On and Off the relay output). 4 – NTC Error (when no NTC sensor is detected or when it is damaged). 5 – NTC and Relay Off Error (when no NTC sensor is detected or when it is damaged and unable to switch Off the relay output). 6 – NTC and Relay On Error (when no NTC sensor is detected or when it is damaged and unable to switch On the relay output). 7 – NTC and Relay On & Off Error (when no NTC sensor is detected or when it is damaged and unable to switch On and Off the relay output). | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
1 | 0 | 1 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | Disable “System Failure” notification | ||||
1 (2) | Ennable “System Failure” notification | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
150 | 4 | RELAY CONTROL SCENARIO 10 | The actual parameter number is 50 when the device is in the 'Binary Switch' mode. Relay 10 Control by Scenario In these parameters, the relay state changes depending on day and time. For these configurations, parameter values are encoded as 7-digit numbers (ABCDEFG). A: State. 0 = Disabled, 1 = Enabled B: Day of week 0 = every day 1-7 = corresponding day (1 is Monday, 7 is Sunday) 8 = every weekday (Monday - Friday) 9 = every weekend (Saturday and Sunday) C: Change state to 0 = Switch OFF 1 = Switch ON DEFG: Time DE represents Hour (from 0 to 23), FG represents Minutes (from 0 to 59). | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1912359 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
1000000 | Relay 10 Control Scenario | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
151 | 4 | RESERVED | The actual parameter number is 51 when the device is in the 'Binary Switch' mode. For 'Binary Switch' device type the parameters from 51 to 60 are reserved by the manufacturer. Setting this parameters will have no impact on DUT functionality. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 4294967295 | No | No | No |
Value |
Description |
||||
0 | Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
16 | 2 | TEMPERATURE RISE NOTIFICATION | Temperature Rise Notification. Use this parameter if you want to know about temperature rise before it reaches the critical value, defined in the “Overheat Protection” parameter. The device will send “Rapid Temperature Rise” notification to the gateway if the temperature sensor reading reaches the value defined in this parameter. The factory default value is 50 in °C scale and 122 in °F scale. Note: We recommend setting the value of this Parameter lower than value of Parameter 17 (Overheat Protection). | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
50 | 0 | 248 | No | No | No |
Value |
Description |
||||
0 | Disable the notification | ||||
1 | The value can be set from 1 to 120 in °C scale mode or from 32 to 248 in °F scale mode. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
17 | 2 | OVERHEAT PROTECTION LEVEL | Overheat Protection & Notification. You can define the maximum limit of temperature, reaching which the device will automatically switch Off the load and send “Overheat Detected” notification to the gateway. The factory default value is 60 in °C scale and 140 in °F scale. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
60 | 0 | 248 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
1 | The value of this parameter can be set from 1 to 120 in °C scale mode or from 32 to 248 in °F scale mode. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
18 | 1 | OVERCURRENT NOTIFICATION | Over-Current Protection & Notification. The maximum load for the device is 16A. If the connected load current exceeds 16A the device will automatically switch Off the output and send the “Over-Current Detected” notification to the gateway. Note: Even if you turn off the notification, the device will switch Off the load when the current reaches 16A. Note: The protection works only if the device is AC powered. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
1 | 0 | 1 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | Disable sending the notification | ||||
1 (2) | Enable sending the notification | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
19 | 2 | OVERLOAD PROTECTION LEVEL | Over-Load Protection & Notification. You can define the maximum power in Watt for connected load. The device will automatically switch off the output and send “Over-Load Detected” notification to the gateway if power consumed by the connected load exceeds this limit. Note: The protection works only if the device is AC powered. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
3500 | 0 | 4000 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
100 | Maximum power in Watt for connected load | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
2 | 1 | FREQUENCY REGION | Frequency Region. The HLS01 has Z-Wave 700 platform chip inside which allows to use the device in different Z-Wave frequencies. If there is a need to use the device in the frequency different from the factory default change the value of this parameter according to the list is user manual. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 9 | No | No | No |
Value |
Description |
||||
0 | Select the corresponding region frequency | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
20 | 2 | OVERVOLTAGE PROTECTION LEVEL | Over-Voltage Protection & Notification. The device constantly monitors the voltage of your electricity network. You can define the maximum voltage of network exceeding which the device will automatically switch off the output and send “Over-Voltage Detected” notification to the gateway. The value of this parameter can be set from 120 to 280 in volts. Note: The protection works only if the device is AC powered. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
240 | 0 | 280 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
120 | Maximum voltage of network exceeding which the device will automatically switch off the output and send “Over-Voltage Detected” notification to the gateway. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
21 | 2 | VOLTAGE DROP PROTECTION LEVEL | Voltage Drop Protection & Notification. You can define the minimum voltage of your electricity network. If the voltage of the network drops determined level the device will automatically switch off the output and send “Voltage Drop Detected” notification to the gateway. Note: The protection works only if the device is AC powered. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
200 | 0 | 240 | No | No | No |
Value |
Description |
||||
0 | Disable the functionality | ||||
80 | Minimum voltage of your electricity network. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
22 | 1 | SPARK PROTECTION | Sparks Protection & Notification. If connected load fails it can create sparks that may cause a fire. The device constantly monitors the power consumption of connected load and can detect even a small surge in consumption and automatically switch off the output and send “Surge Detected” notification to the gateway. Note: The protection works only if the device is AC powered. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
1 | 0 | 1 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | Disable Sparks Protection & Notification | ||||
1 (2) | Enable Sparks Protection & Notification | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
23 | 4 | RESERVED | Parameters from 23 to 30 are reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 4294967295 | No | No | No |
Value |
Description |
||||
0 | Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
3 | 1 | OUTPUT MODE | Output NO/NC Mode. The device can operate in Normal Open (NO) mode and in Normal Close (NC) mode. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | The device switch operates in NO mode and there is no voltage on output when the device is in OFF state. The output will be powered when device goes to ON state. | ||||
1 (2) | The output will be powered in OFF state and will be no voltage on output when the device is in ON state. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
31 | 1 | LOAD ERROR NOTIFICATION | Parameter only for 'Thermostat' device type: Load Error Notification. The device can send the “Load Error” notification to the gateway when the relay is On but there is no power consumption (meaning possible problems with the heating system). Note: The function works only if the device is AC powered. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 1 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | Disable sending the notification | ||||
1 (2) | Disable sending the notification | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
32 | 1 | TEMPERATURE REGULATION HYSTERESYS | Parameter only for 'Thermostat' device type: Temperature Hysteresis. This Parameter defines the hysteresis value for temperature control. The HE-HLS01 will stabilize the temperature with selected hysteresis. For example, if the SET POINT is set for 25°C and HYSTERESIS is set for 0.5°C the HE-HLS01 will change the state to IDLE when the temperature reaches 25.0°C, but it will change the state to HEATING if the temperature drops lower than 24.5°C. The hysteresis can be changed from 0.2°C to 10.0°C range in Celsius mode, and from 1°F to 18.0°F in Fahrenheit mode. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
5 | 2 | 100 | No | No | No |
Value |
Description |
||||
2 | Hysteresis value for temperature control. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
33 | 1 | BASIC SET MODE | Parameter only for 'Thermostat' device type: Basic Set Action This Parameter defines which Operating Mode the HE-HLS01 reverts to if the Basic Set command is received. If the Basic Set command value is 0 (OFF state) the HE-HLS01 will go to Manual mode and switch Off the heating element (IDLE mode). If the Basic Set command is value is 0xFF (ON state) the HE-HLS01 will change the Mode to the corresponding Parameter value. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
1 | 1 | 5 | No | No | No |
Bit (Value) |
Description |
||||
1 (2) | HEAT mode | ||||
2 (4) | AUTO mode | ||||
3 (8) | DRY mode | ||||
4 (16) | ECO mode | ||||
5 (32) | VAC mode | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
34 | 1 | S1 INPUT MODE | Parameter only for 'Thermostat' device type: S1 external input mode | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 3 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | The input state changes will be ignored by the Thermostat logic | ||||
1 (2) | The external input will operate in “Toggle Switch” mode: if the external input is shorted (with Sx or Line) the Thermostat switches to the operating mode selected in the Parameter 35 and switches to OFF mode when the external input is open. | ||||
2 (4) | The external input will operate in “Toggle Switch Reverse” mode: if the external input is shorted the Thermostat switches to OFF mode and switches to the operating mode selected in the Parameter 35 when the input is open. | ||||
3 (8) | The external input will operate in “Push Button (Momentary Switch)” mode: each press of button (shorten of input) will consistently change the mode to the operating mode selected in the Parameter 35. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
35 | 1 | S1 INPUT ACTION | Parameter only for 'Thermostat' device type: Mode number for S1 external input action | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
1 | 1 | 5 | No | No | No |
Bit (Value) |
Description |
||||
1 (2) | HEAT mode | ||||
2 (4) | AUTO mode | ||||
3 (8) | DRY mode | ||||
4 (16) | ECO mode | ||||
5 (32) | VAC mode | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
36 | 2 | DRY TIME | Parameter only for 'Thermostat' device type: Dry Mode Timeout. By choosing Dry Mode, the device will increase the temperature to the selected Set Point and keep it for the time specified in this parameter. As the Dry Time passes, the Thermostat will automatically change to the Mode set in the Parameter 37. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
30 | 1 | 720 | No | No | No |
Value |
Description |
||||
1 | A time range of 1 to 720 minutes (12 hours) can be set. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
37 | 1 | DRY MODE SWITCH | Parameter only for 'Thermostat' device type: Mode to switch after Dry mode operation completion | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
1 | 1 | 6 | No | No | No |
Bit (Value) |
Description |
||||
1 (2) | HEAT mode | ||||
2 (4) | AUTO mode | ||||
4 (16) | ECO mode | ||||
5 (32) | VAC mode | ||||
6 (64) | OFF mode | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
38 | 2 | MORNING START TIME | Parameter only for 'Thermostat' device type: Morning start time. Format: HHMM. e.g.08:00 should be sent as 0800 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
600 | 0 | 2359 | No | No | No |
Value |
Description |
||||
0 | Morning start time. Format: HHMM (from 00:00 to 23:59) | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
39 | 2 | DAY START TIME | Parameter only for 'Thermostat' device type: Day start time. Format: HHMM. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
900 | 0 | 2359 | No | No | No |
Value |
Description |
||||
0 | Day start time. Format: HHMM (from 00:00 to 23:59) | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
4 | 1 | TIME CORRECTION | Time correction by controller | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
1 | 0 | 1 | No | No | No |
Bit (Value) |
Description |
||||
0 (1) | Switch off auto-correction | ||||
1 (2) | If the device is connected to a Z-Wave gateway, the time and day will be periodically polled and corrected from the gateway | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
40 | 2 | EVENING START TIME | Parameter only for 'Thermostat' device type: Evening start time. Format: HHMM. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
1800 | 0 | 2359 | No | No | No |
Value |
Description |
||||
0 | Evening start time. Format: HHMM (from 00:00 to 23:59) | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
41 | 2 | NIGHT START TIME | Parameter only for 'Thermostat' device type: Night start time. Format: HHMM. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
2300 | 0 | 2359 | No | No | No |
Value |
Description |
||||
0 | Night start time. Format: HHMM (from 00:00 to 23:59) | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
42 | 2 | MONDAY MORNING TEMP | Parameter only for 'Thermostat' device type: Monday Morning temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
240 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Monday Morning temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
43 | 2 | MONDAY DAYTIME TEMP | Parameter only for 'Thermostat' device type: Monday Day temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
200 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Monday Day temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
44 | 2 | MONDAY EVENING TEMP | Parameter only for 'Thermostat' device type: Monday Evening temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
230 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Monday Evening temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
45 | 2 | MONDAY NIGHT TEMP | Parameter only for 'Thermostat' device type: Monday Night temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
180 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Monday Night temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
46 | 2 | TUESDAY MORNING TEMP | Parameter only for 'Thermostat' device type: Tuesday Morning temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
240 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Tuesday Morning temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
47 | 2 | TUESDAY DAYTIME TEMP | Parameter only for 'Thermostat' device type: Tuesday Day temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
200 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Tuesday Day temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
48 | 2 | TUESDAY EVENING TEMP | Parameter only for 'Thermostat' device type: Tuesday Evening temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
230 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Tuesday Evening temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
49 | 2 | TUESDAY NIGHT TEMP | Parameter only for 'Thermostat' device type: Tuesday Night temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
180 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Tuesday Night temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
5 | 1 | WEEKDAY | Week day. Allows manually adjustment of the day of the week in case the HE-HLS01 is not connected to any Z-Wave gateway or the Parameter 04 (auto-correction) is set to 0. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
1 | 1 | 7 | No | No | No |
Bit (Value) |
Description |
||||
1 (2) | Monday | ||||
2 (4) | Tuesday | ||||
3 (8) | Wednesday | ||||
4 (16) | Thursday | ||||
5 (32) | Friday | ||||
6 (64) | Saturday | ||||
7 (128) | Sunday | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
50 | 2 | WEDNESDAY MORNING TEMP | Parameter only for 'Thermostat' device type: Wednesday Morning temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
240 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Wednesday Morning temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
51 | 2 | WEDNESDAY DAYTIME TEMP | Parameter only for 'Thermostat' device type: Wednesday Day temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
200 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Wednesday Day temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
52 | 2 | WEDNESDAY EVENING TEMP | Parameter only for 'Thermostat' device type: Wednesday Evening temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
230 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Wednesday Evening temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
53 | 2 | WEDNESDAY NIGHT TEMP | Parameter only for 'Thermostat' device type: Wednesday Night temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
180 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Wednesday Night temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
54 | 2 | THURSDAY MORNING TEMP | Parameter only for 'Thermostat' device type: Thursday Morning temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
240 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Thursday Morning temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
55 | 2 | THURSDAY DAYTIME TEMP | Parameter only for 'Thermostat' device type: Thursday Day temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
200 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Thursday Day temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
56 | 2 | THURSDAY EVENING TEMP | Parameter only for 'Thermostat' device type: Thursday Evening temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
230 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Thursday Evening temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
57 | 2 | THURSDAY NIGHT TEMP | Parameter only for 'Thermostat' device type: Thursday Night temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
180 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Thursday Night temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
58 | 2 | FRIDAY MORNING TEMP | Parameter only for 'Thermostat' device type: Friday Morning temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
240 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Friday Morning temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
59 | 2 | FRIDAY DAYTIME TEMP | Parameter only for 'Thermostat' device type: Friday Day temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
200 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Friday Day temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
6 | 1 | HOUR | Time hour. Allows manually adjustment of hours for internal clock in case the HE-HLS01 is not connected to any Z-Wave gateway or the Parameter 04 (auto-correction) is set to 0. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 23 | No | No | No |
Value |
Description |
||||
0 | This Parameter allows manual adjustment of Time in hours (24 hours). | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
60 | 2 | FRIDAY EVENING TEMP | Parameter only for 'Thermostat' device type: Friday Evening temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
230 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Friday Evening temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
61 | 2 | FRIDAY NIGHT TEMP | Parameter only for 'Thermostat' device type: Friday Night temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
180 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Friday Night temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
62 | 2 | SATURDAY MORNING TEMP | Parameter only for 'Thermostat' device type: Saturday Morning temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
240 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Saturday Morning temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
63 | 2 | SATURDAY DAYTIME TEMP | Parameter only for 'Thermostat' device type: Saturday Day temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
200 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Saturday Day temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
64 | 2 | SATURDAY EVENING TEMP | Parameter only for 'Thermostat' device type: Saturday Evening temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
230 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Saturday Evening temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
65 | 2 | SATURDAY NIGHT TEMP | Parameter only for 'Thermostat' device type: Saturday Night temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
180 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Saturday Night temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
66 | 2 | SUNDAY MORNING TEMP | Parameter only for 'Thermostat' device type: Sunday Morning temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
240 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Sunday Morning temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
67 | 2 | SUNDAY DAYTIME TEMP | Parameter only for 'Thermostat' device type: Sunday Day temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
200 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Sunday Day temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
68 | 2 | SUNDAY EVENING TEMP | Parameter only for 'Thermostat' device type: Sunday Evening temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
230 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Sunday Evening temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
69 | 2 | SUNDAY NIGHT TEMP | Parameter only for 'Thermostat' device type: Sunday Night temperature, valueX10 | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
180 | 10 | 1100 | No | No | No |
Value |
Description |
||||
10 | Sunday Night temperature value | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
7 | 1 | MINUTE | Time minutes. Allows manually adjustment of minutes for internal clock in case the HE-HLS01 is not connected to any Z-Wave gateway or the Parameter 04 (auto-correction) is set to 0. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 59 | No | No | No |
Value |
Description |
||||
0 | This Parameter allows manual adjustment of the Time in minutes (60 minutes)) | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
70 | 4 | RESERVED | For 'Thermostat' device type the parameters from 70 to 80 are reserved by the manufacturer. Setting this parameters will have no impact on DUT functionality. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | 0 | 4294967295 | No | No | No |
Value |
Description |
||||
0 | Parameter reserved by the manufacturer. Setting this parameter will have no impact on DUT functionality. | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
8 | 1 | NTC RESISTANCE | External NTC Temperature Sensor Resistance (kΩ) | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
10 | 1 | 100 | No | No | No |
Value |
Description |
||||
1 | Floor Sensor Resistance in kiloOhms (kΩ) | ||||
Parameter Number |
Parameter Size |
Parameter Name |
Description |
||
9 | 1 | TEMPERATURE SENSOR OFFSET | Temperature Calibration in °C, x10. Temperature Sensor Calibration This Parameter defines the offset value for external NTC temperature sensor. If the temperature sensor is not calibrated properly, manual calibration can be made by adjusting the values up to ±10.0°C or ±18°F. | ||
Default Value |
Minimum Value |
Maximum Value |
Read Only |
Re-Inclusion |
Advanced |
0 | -100 | 100 | No | No | No |
From |
To |
Description |
|||
-100 | 100 | This value will be added or subtracted from the temperature sensor reading | |||