Z-Wave Products

TThere are thousands of interoperable Z-Wave products throughout the world, and over 94 million Z-Wave products have been sold since our beginnings in 2001. All of them work together regardless of brand, because they're all based on the common Z - Wavestandard.Browse our Product Finder to see what Z -Wave can do for you.

Z-Wave Configuration Capabilities

Model: Radio I/O Modul (MTIOM-100-WL)

Z-Wave Certification Number: ZC12-21020178


Parameter Number

Parameter Size

Parameter Name

Description

1 2 Heartbeat rate [min] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

60 1 1440 No No No

Value

 

Description

1   Value tells at what interval [min] Heartbeat will be sent

Parameter Number

Parameter Size

Parameter Name

Description

10 2 DI 5 send enable see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 2 No No No

Value

 

Description

0   Notifications for DI 5 are disabled
1   Binary Sensor Report for DI 5 is enabled
2   Central Scene Report for DI 5 is enabled

Parameter Number

Parameter Size

Parameter Name

Description

11 2 DI 5 send interval [min] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

50 1 1200 No No No

Value

 

Description

1   Value tells at what interval [0.1min] notification for DI 5 will we sent

Parameter Number

Parameter Size

Parameter Name

Description

12 2 DI 6 send enable see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 2 No No No

Value

 

Description

0   Notifications for DI 6 are disabled
1   Binary Sensor Report for DI 6 is enabled
2   Central Scene Report for DI 6 is enabled

Parameter Number

Parameter Size

Parameter Name

Description

13 2 DI 6 send interval [min] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

50 1 1200 No No No

Value

 

Description

1   Value tells at what interval [0.1min] notification for DI 6 will we sent

Parameter Number

Parameter Size

Parameter Name

Description

14 2 AI 1 send enable see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Sending AI 1 values disabled
1   Sending AI 1 values enabled

Parameter Number

Parameter Size

Parameter Name

Description

15 2 AI 1 sensor select see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 5 No No No

Value

 

Description

0   Configure AI 1 for NTC 5k Ohm thermistor
1   Configure AI 1 for NTC 10k Ohm thermistor
2   Configure AI 1 for PTC 1k Ohm thermistor
3   Configure AI 1 for PT1000 thermistor
4   Configure AI 1 for 0 - 10V sensor
5   Configure AI 1 for digital input

Parameter Number

Parameter Size

Parameter Name

Description

16 2 AI 1 send interval [min] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

50 1 1200 No No No

Value

 

Description

1   Value tells at what interval [0.1min] sensor values for AI 1 will be sent

Parameter Number

Parameter Size

Parameter Name

Description

17 2 AI 1 send delta temp [K] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 100 No No No

From

 

To

Description

1   100 Value tells at what temperature difference [0.1K]for AI 1 will be sent

Parameter Number

Parameter Size

Parameter Name

Description

18 2 AI 1 send delta volt [V] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 100 No No No

Value

 

Description

1   Value tells at what voltage difference [0.1V]for AI 1 will be sent

Parameter Number

Parameter Size

Parameter Name

Description

19 2 AI 2 send enable see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Sending AI 2 values disabled
1   Sending AI 2 values enabled

Parameter Number

Parameter Size

Parameter Name

Description

2 2 DI 1 send enable see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 2 No No No

Value

 

Description

0   Notifications for DI 1 are disabled
1   Binary Sensor Report for DI 1 is enabled
2   Central Scene Report for DI 1 is enabled

Parameter Number

Parameter Size

Parameter Name

Description

20 2 AI 2 sensor select see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 5 No No No

Value

 

Description

0   Configure AI 2 for NTC 5k Ohm thermistor
1   Configure AI 2 for NTC 10k Ohm thermistor
2   Configure AI 2 for PTC 1k Ohm thermistor
3   Configure AI 2 for PT1000 thermistor
4   Configure AI 2 for 0 - 10V sensor
5   Configure AI 2 for digital input

Parameter Number

Parameter Size

Parameter Name

Description

21 2 AI 2 send interval [min] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

50 1 1200 No No No

Value

 

Description

1   Value tells at what interval [0.1min] sensor values for AI 2 will be sent

Parameter Number

Parameter Size

Parameter Name

Description

22 2 AI 2 send delta temp [K] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 100 No No No

From

 

To

Description

1   100 Value tells at what temperature difference [0.1K]for AI 2 will be sent

Parameter Number

Parameter Size

Parameter Name

Description

23 2 AI 2 send delta volt [V] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 100 No No No

Value

 

Description

1   Value tells at what voltage difference [0.1V]for AI 2 will be sent

Parameter Number

Parameter Size

Parameter Name

Description

24 2 AI 3 send enable see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Sending AI 3 values disabled
1   Sending AI 3 values enabled

Parameter Number

Parameter Size

Parameter Name

Description

25 2 AI 3 sensor select see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 5 No No No

Value

 

Description

0   Configure AI 3 for NTC 5k Ohm thermistor
1   Configure AI 3 for NTC 10k Ohm thermistor
2   Configure AI 3 for PTC 1k Ohm thermistor
3   Configure AI 3 for PT1000 thermistor
4   Configure AI 3 for 0 - 10V sensor
5   Configure AI 3 for digital input

Parameter Number

Parameter Size

Parameter Name

Description

26 2 AI 3 send interval [min] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

50 1 1200 No No No

Value

 

Description

1   Value tells at what interval [0.1min] sensor values for AI 3 will be sent

Parameter Number

Parameter Size

Parameter Name

Description

27 2 AI 3 send delta temp [K] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 100 No No No

From

 

To

Description

1   100 Value tells at what temperature difference [0.1K]for AI 3 will be sent

Parameter Number

Parameter Size

Parameter Name

Description

28 2 AI 3 send delta volt [V] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 100 No No No

Value

 

Description

1   Value tells at what voltage difference [0.1V]for AI 3 will be sent

Parameter Number

Parameter Size

Parameter Name

Description

29 2 AI 4 send enable see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Sending AI 4 values disabled
1   Sending AI 4 values enabled

Parameter Number

Parameter Size

Parameter Name

Description

3 2 DI 1 send interval [min] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

50 1 1200 No No No

Value

 

Description

1   Value tells at what interval [0.1min] notification for DI 1 will we sent

Parameter Number

Parameter Size

Parameter Name

Description

30 2 AI 4 sensor select see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 5 No No No

Value

 

Description

0   Configure AI 4 for NTC 5k Ohm thermistor
1   Configure AI 4 for NTC 10k Ohm thermistor
2   Configure AI 4 for PTC 1k Ohm thermistor
3   Configure AI 4 for PT1000 thermistor
4   Configure AI 4 for 0 - 10V sensor
5   Configure AI 4 for digital input

Parameter Number

Parameter Size

Parameter Name

Description

31 2 AI 4 send interval [min] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

50 1 1200 No No No

Value

 

Description

1   Value tells at what interval [0.1min] sensor values for AI 4 will be sent

Parameter Number

Parameter Size

Parameter Name

Description

32 2 AI 4 send delta temp [K] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 100 No No No

From

 

To

Description

1   100 Value tells at what temperature difference [0.1K]for AI 4 will be sent

Parameter Number

Parameter Size

Parameter Name

Description

33 2 AI 4 send delta volt [V] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 100 No No No

Value

 

Description

1   Value tells at what voltage difference [0.1V]for AI 4 will be sent

Parameter Number

Parameter Size

Parameter Name

Description

4 2 DI 2 send enable see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 2 No No No

Value

 

Description

0   Notifications for DI 2 are disabled
1   Binary Sensor Report for DI 2 is enabled
2   Central Scene Report for DI 2 is enabled

Parameter Number

Parameter Size

Parameter Name

Description

5 2 DI 2 send interval [min] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

50 1 1200 No No No

Value

 

Description

1   Value tells at what interval [0.1min] notification for DI 2 will we sent

Parameter Number

Parameter Size

Parameter Name

Description

6 2 DI 3 send enable see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 2 No No No

Value

 

Description

0   Notifications for DI 3 are disabled
1   Binary Sensor Report for DI 3 is enabled
2   Central Scene Report for DI 3 is enabled

Parameter Number

Parameter Size

Parameter Name

Description

7 2 DI 3 send interval[min] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

50 1 1200 No No No

Value

 

Description

1   Value tells at what interval [0.1min] notification for DI 3 will we sent

Parameter Number

Parameter Size

Parameter Name

Description

8 2 DI 4 send enable see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 2 No No No

Value

 

Description

0   Notifications for DI 4 are disabled
1   Binary Sensor Report for DI 4 is enabled
2   Central Scene Report for DI 4 is enabled

Parameter Number

Parameter Size

Parameter Name

Description

9 2 DI 4 send interval [min] see manual

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

50 1 1200 No No No

Value

 

Description

1   Value tells at what interval [0.1min] notification for DI 4 will we sent