TThere are thousands of interoperable Z-Wave products throughout the world, and over 94 million Z-Wave products have been sold since our beginnings in 2001. All of them work together regardless of brand, because they're all based on the common Z - Wavestandard.Browse our Product Finder to see what Z -Wave can do for you.

Z-Wave Configuration Capabilities

Model: Air quality sensor (SZ-AIR-HTQ01)

Z-Wave Certification Number: ZC12-21010171


Parameter Number

Parameter Size

Parameter Name

Description

1 2 CC_TYPE_COMMAND_MIN_TEMPERATURE Set minimal temperature

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

18 1 18 No No No

From

 

To

Description

1   18 The minimum temperature in degrees Celcius

Parameter Number

Parameter Size

Parameter Name

Description

12 2 CC_TYPE_COMMAND_TIME_REPORT Set times report

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

300 60 10800 No No No

Value

 

Description

60   The interval between readings sending

Parameter Number

Parameter Size

Parameter Name

Description

13 2 CC_TYPE_COMMAND_TEMPERATURE_REPORT Set delta temperature report

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

1 1 10 No No No

Value

 

Description

1   The change in temperature values at which the report sending occurs

Parameter Number

Parameter Size

Parameter Name

Description

14 2 CC_TYPE_COMMAND_HUMIDITY_REPORT Set delta humidity report

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5 1 10 No No No

Value

 

Description

1   Humidity value change at which the sending occurs

Parameter Number

Parameter Size

Parameter Name

Description

15 2 CC_TYPE_COMMAND_CO2_REPORT Set delta CO2 report

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

50 10 1000 No No No

Value

 

Description

10   CO2 value change at which the sending occurs

Parameter Number

Parameter Size

Parameter Name

Description

16 2 CC_TYPE_COMMAND_TVOC_REPORT Set delta tVOC report

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

100 10 1000 No No No

Value

 

Description

10   tVOC value change at which the sending occurs

Parameter Number

Parameter Size

Parameter Name

Description

2 2 CC_TYPE_COMMAND_MAX_TEMPERATURE Set maximum temperature

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

27 27 80 No No No

From

 

To

Description

27   80 The maximum temperature in degrees Celcius

Parameter Number

Parameter Size

Parameter Name

Description

3 2 CC_TYPE_COMMAND_MAX_CO2 Set maximum level CO2

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

750 400 3000 No No No

Value

 

Description

400   The maximum level of CO2 in ppm

Parameter Number

Parameter Size

Parameter Name

Description

4 2 CC_TYPE_COMMAND_MIN_TVOC Set minimum level tVOC

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

65 0 99 No No No

Value

 

Description

0   The minimum level of total volitile organic compound in ppb

Parameter Number

Parameter Size

Parameter Name

Description

5 2 CC_TYPE_COMMAND_MID_TVOC Set middle level tVOC

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

550 100 1000 No No No

Value

 

Description

100   The average level of total volitile organic compound in ppb

Parameter Number

Parameter Size

Parameter Name

Description

6 2 CC_TYPE_COMMAND_MAX_TVOC Set maximum level tVOC

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

5000 1001 5000 No No No

Value

 

Description

1001   The maximum level of total volitile organic compound in ppb

Parameter Number

Parameter Size

Parameter Name

Description

7 2 CC_TYPE_COMMAND_INDICATE_CONTROL Set indicate control

Default Value

Minimum Value

Maximum Value

Read Only

Re-Inclusion

Advanced

0 0 1 No No No

Value

 

Description

0   Enable (1) or disable (0) air quality indication