25 | Configurable Terminal Setting | Control the function of the configurable terminal on the thermostat. | 0 | 1 | 0 | 0 | 0 | From | To | Description |
---|
2 | 2 | H | 1 | 1 | W3 | 0 | 0 | Disabled | 3 | 3 | DH |
|
2 | Heat Stages | Number of heat stages if HVAC type is normal or number of auxiliary heat stages if HVAC type is heat pump. | 0 | 1 | 0 | 0 | 2 | From | To | Description |
---|
0 | 3 | Number of Heat Stages |
|
3 | Number of Cool Stages | Number of cool stages if normal or the number of heat pump stages if heat pump | 0 | 1 | 0 | 0 | 2 | From | To | Description |
---|
0 | 2 | Cool Stages |
|
4 | Heat Fuel Type | Denotes the heating fuel type. | 0 | 1 | 0 | 0 | 1 | From | To | Description |
---|
1 | 1 | Electric (default) | 0 | 0 | Fossil Fuel |
|
1 | HVAC System Type | The type of HVAC system, either normal or heat pump. | 0 | 1 | 0 | 0 | 0 | From | To | Description |
---|
0 | 0 | Normal | 1 | 1 | Heat Pump |
|
5 | Calibration Temperature | Used to adjust the ambient room temperature reading up or down to a more accurate value. This may be necessary if the thermostat is installed in a location with abnormal temperature conditions, such as in direct sunlight, near an open window, or on a wall adjacent to an unheated room. The value should be in 1.0 degree Fahrenheit increments. For example, to set the calibration to 2.0F, use value 20. | 0 | 4 | 0 | 0 | 0 | From | To | Description |
---|
-100 | 100 | Calibration Temperature Range (in deg. F) Precision is tenths of a degree. |
|
8 | Heat Staging Delay | In a multistage system, the number of minutes the thermostat will wait before turning on the next heating stage. | 0 | 1 | 0 | 0 | 5 | From | To | Description |
---|
1 | 60 | Heat Staging Delay (in min) |
|
10 | Balance Setpoint | If the outside temperature falls below the balance setpoint, the thermostat will only use Auxiliary heating to heat and will not use the heat pump. The value should be in 1.0 degree Fahrenheit increments. For example, to set the balance setpoint to 45.0F, use value 450. | 0 | 4 | 0 | 0 | 350 | From | To | Description |
---|
0 | 950 | Balance Setpont Range (in deg. F) Precision is tenths of a degree. |
|
9 | Cool Staging Delay | In a multistage system, the number of minutes the thermostat will wait before turning on the next cooling stage. | 0 | 1 | 0 | 0 | 5 | From | To | Description |
---|
1 | 60 | Cool Staging Delay (in min) |
|
23 | Temperature Display Units | This parameter controls what thermostat units are displayed on the thermostat screen. It is independent of the temperature units used on the Z-Wave network. | 0 | 1 | 0 | 0 | 1 | From | To | Description |
---|
0 | 0 | Celsius | 1 | 1 | Farenheit |
|
11 | Recovery Settings | In a multistage system, the thermostat will use all stages to reach the target when in comfort mode. When in efficient mode, the thermostat will only use all stages to get within the differential temperature, at which time it will only use a single stage. | 0 | 1 | 0 | 0 | 1 | From | To | Description |
---|
0 | 0 | Comfort | 1 | 1 | Efficient |
|
17 | Maximum Cool Setpoint | Maximum cool target allowed. Attempts to set the cool target higher than this value will be ignored. The value should be in 1.0 degree Fahrenheit increments. For example, to set the maximum cool setpoint to 80.0F, use value 800. | 0 | 4 | 0 | 0 | 950 | From | To | Description |
---|
500 | 950 | Max Cool Setpoint Range(in deg. F) Precision is tenths of a degree. |
|