1 | In-wall Switch Type for Load to control I1 | With this parameter, you can select between push-button (momentary) and on/off toggle switch types. | 0 | 1 | 0 | 0 | 0 | From | To | Description |
|---|
0 | 0 | push-button (momentary) | 1 | 1 | on/off toggle switch |
|
65 | Dimming time when key pressed (soft on/off) | Choose the time during which the device will move between the min. and max. dimming values by a short press of the push-button I1. | 0 | 1 | 0 | 0 | 1 | From | To | Description |
|---|
1 | 1 | 1 second | 1 | 127 | 1 seconds- 127 seconds, step is 1 second |
|
68 | Dimming duration | Choose the time during which the device will transition from the current value to the new target value. This parameter applies to the association group 3. NOTE: Parameter is valid only in Dimmer mode. In Switch mode the parameter has no effect. | 0 | 1 | 0 | 0 | 0 | From | To | Description |
|---|
0 | 0 | dimming duration according to parameter 66 | 1 | 127 | from 1 to 127 seconds |
|
72 | Calibration status (read only) | With this parameter you can check the calibration status. | 0 | 1 | 0 | 0 | 2 | From | To | Description |
|---|
1 | 1 | calibration was successful | 2 | 2 | calibration failed |
|
70 | Overload safety switch | The function allows for turning off the controlled device in case of exceeding the defined power for more than 5s. Controlled device can be turned back on by input I1 or sending a control frame. ⓘ NOTE: This functionality is not an overload safety protection, please check the technical specifications chapter for more details. In case of overload the following message will be send towards the controller: • COMMAND_CLASS_NOTIFICATION_V5 • The Alarm V1 type field set to 0x00 • Notification Type 0x08 and 0x08 (Overload detected) | 0 | 2 | 0 | 0 | 200 | From | To | Description |
|---|
0 | 0 | function not active | 1 | 200 | 1W - 200W |
|
73 | Alarm/Notification events | This parameter defines the module behaviour in case it receives any Alarm/Notification events. NOTE: When value 3 is selected the default time interval of the blinking is 10 minutes. It can be stopped with a button press or sending a control frame. To adjust the time interval please refer to parameter 74 – Alarm/Notification time interval. | 0 | 1 | 0 | 0 | 0 | From | To | Description |
|---|
1 | 1 | turn OFF | 2 | 2 | turn ON | 3 | 3 | start blinking (output turns 1s ON, and 1s OFF) |
|
60 | Minimum dimming value | The value set in this parameter determines the minimum dimming value (the lowest value which can be set on the device, when, for example, dimming lights with wall switch or slider in the GUI (Gateway - hub)) (Data type 1 byte dec) • default value 0 = 0% (minimum dimming value) • 0- 98 = 0% - 98%, step is 1%. Minimum dimming value is set by entering a value. ⓘ NOTE: The minimum level may not be higher than the maximum level! | 0 | 1 | 0 | 0 | 0 | From | To | Description |
|---|
0 | 98 | 0% - 98%, step is 1%. Minimum dimming value is set by entering a value | 0 | 0 | 0% (minimum dimming value) |
|
61 | Maximum dimming value | The value set in this parameter determines the maximum dimming value (the highest value which can be set on the device, when, for example, dimming lights with wall switch or slider in the GUI (Gateway - hub)) ⓘ NOTE: The maximum level may not be lower than the minimum level! | 0 | 1 | 0 | 0 | 99 | From | To | Description |
|---|
1 | 99 | 1% - 99%, step is 1%. Maximum dimming value is set by entering a value. | 99 | 99 | 99% (Maximum dimming value) |
|
66 | Dimming time when key hold | Choose the time during which the Dimmer will move between the min. and max. dimming values during a continuous press of the push-button I1, by an associated device or through the UI controls (BasicSet, SwitchMultilevelSet). | 0 | 2 | 0 | 0 | 3 | From | To | Description |
|---|
1 | 127 | 1 second – 127 seconds | 128 | 253 | 1 minute – 126 minutes |
|
71 | Calibration trigger | Choose when will be the calibration procedure triggered. | 0 | 1 | 0 | 0 | 0 | From | To | Description |
|---|
1 | 1 | calibration done after power cycle regardless of inclusion status | 2 | 2 | force calibration. Calibration will start immediately |
|
74 | Alarm/Notification time interval (dependant on parameter 73) | This parameter defines the time interval of the blinking state, once the module receives an alarm/notification event. Minimum step increase is 1 minute. NOTE: This parameter does not have any effect if parameter 73 is not set to value 3. | 0 | 1 | 0 | 0 | 10 | From | To | Description |
|---|
1 | 125 | 1-125 minutes |
|
67 | Ignore start level | Choose whether the device should use (or disregard) the start dimming level value. If the device is configured to use the start level, it should start the dimming process from the currently set dimming level. This parameter is used with association group 3. NOTE: Parameter is valid only in Dimmer mode. In Switch mode the parameter has no effect. | 0 | 1 | 0 | 0 | 0 | From | To | Description |
|---|
0 | 0 | use the start level value | 1 | 1 | ignore the start level value |
|
5 | Working mode | With this parameter, you can change the device presentation on the user interface. ⓘ NOTE: After parameter change, first exclude the device (without setting parameters to default value) then wait at least 30s before reinclusion. | 0 | 1 | 0 | 0 | 0 | From | To | Description |
|---|
1 | 1 | Switch mode (works only in 3 way wiring-connection with neutral line) | 0 | 0 | Dimmer mode |
|
11 | Turn Load 1 Off Automatically with Timer | If Load is ON, you can schedule it to turn OFF automatically after a period of time defined in this parameter. The timer is reset to zero each time the device receives an ON or OFF command, either remotely (from the gateway (hub) or associated device) or locally from the switch. | 0 | 2 | 0 | 0 | 0 | From | To | Description |
|---|
0 | 0 | Auto OFF Disabled | 1 | 32536 | 1 - 32536 seconds - Auto OFF timer enabled for a given amount of seconds |
|